Cables are designed for fixed distribution of electricity in ordinary environment in hotels, hospitals, subway, airports, etc., to protect people and technical equipment of buildings in case of fire, where there is requirement to maintain the functionality of the entire cable installation in fire. In case of fire, the cable releases a small amount of heat and smoke. The cables are not UV-resistant.
Design
This product consists of:
1
Copper conductor, round solid (RE) resp. round stranded (RM)
2
Core insulation (silicone rubber)
3
Inner covering (halogen-free bedding compound)
4
Inner sheath (halogen-free polymer compound)
5
Armouring (galvanized steel wires)
6
Sheath (halogen-free polymer compound, brown)
Technical Data
Standard: ČSN 34 7660-100
Certificate: EZÚ Czech Republic
Test Voltage: core/core 4 kV / 50 Hz
Rated Voltage: 0.6/1 kV
Bending radius (min.): 12 x Ø of cable (multicore)
Fire properties:
ČSN EN 60332-1-2: self-extinguishing
ČSN EN 60754-2: halogen-free, non-corrosive combustion gases
ČSN EN 61034-2: low smoke emission
ČSN EN 60332-3-22: reduced flame propagation
ČSN 73 0895, STN 92 0205: circuit integrity
ČSN EN 13501-6: fire classification
CPR Classification: B2ca s1a d1 a1
Core identification: ČSN 33 0166 ed. 2, ČSN EN 50334
Earthing and Short Circuiting Cables and Bare Wires
Instalation and Harmonised Cables and Wires
Low Voltage Cables 0,6/1 kV
Medium Voltage Cables up to 36 kV
Rubber, Silicone and PUR Cables
Commercial Vehicles and EVC Cables
Automation and Motor Supply Cables
Railway Signalling and Telecommunications Cables
Special Cables
Our Code of Conduct and its associated regulations are not seeking to „invent“ new approaches. Instead, they aim to clearly demonstrate the obligations we must fulfill nowadays.