SiR/FRNC halogen-free energy cable with insulation integrity and circuit integrity
Safety Cables with circuit integrity
These cables are intended for the stationary distribution of electrical energy in dry or damp premises and for fixed installations in air or concrete. Suitable for hotels, hospitals, underground railways, airports etc. to protect people and technical building equipment in the event of fire.. Not allowed for installations underground or in water. These cables are not UV-protected.
Design
This product consists of:
1
Copper conductor, round solid (RE) resp. round stranded (RM)
2
Core insulation (silicone rubber)
3
Inner covering (halogen-free fixation tape)
4
Sheath (halogen-free polymer compound, orange)
Technical Data
Standard: adapted to DIN VDE 0266
Certificate: VDE Germany
Test Voltage: core/core 4 kV / 50 Hz
Rated Voltage: 0,6/1 kV
Bending radius (min.):
12 x Ø of cable (multicore)
15 x Ø of cable (singlecore)
Fire properties:
EN 60332-1-2: flame retardant
EN 60754-2: halogen-free, non-corrosive combustion gases
EN IEC 60332-3-24: reduced flame propagation
EN 61034-2: low smoke emission
IEC 60331-21, DIN VDE 0472-814: insulation integrity FE 180
Earthing and Short Circuiting Cables and Bare Wires
Instalation and Harmonised Cables and Wires
Low Voltage Cables 0,6/1 kV
Medium Voltage Cables up to 36 kV
Rubber, Silicone and PUR Cables
Commercial Vehicles and EVC Cables
Automation and Motor Supply Cables
Railway Signalling and Telecommunications Cables
Special Cables