SiR/FRNC halogen-free energy cable with insulation integrity and circuit integrity
Safety Cables
These cables are intended for the stationary distribution of electrical energy in dry or damp premises and for fixed installations in air or concrete. Suitable for hotels, hospitals, underground railways, airports etc. to protect people and technical building equipment in the event of fire.. Not allowed for installations underground or in water. These cables are not UV-protected.
Design
This product consists of:
1
Copper conductor, round solid (RE) resp. round stranded (RM)
2
Core insulation (silicone rubber)
3
Inner covering (halogen-free fixation tape)
4
Sheath (halogen-free polymer compound, orange)
Technical Data
Standard:adapted to DIN VDE 0266
Certificate:VDE Germany
Test Voltage:core/core 4 kV / 50 Hz
Rated Voltage:0,6/1 kV
Bending radius (min.):
12 x Ø of cable (multicore)
15 x Ø of cable (singlecore)
Fire properties:
EN 60332-1-2: flame retardant and self-extinguishing
EN 60754-2: halogen-free, non-corrosive combustion gases
EN IEC 60332-3-24: reduced flame propagation
EN 61034-2: low smoke emission
IEC 60331-21, DIN VDE 0472-814: insulation integrity FE 180