Power distribution and control cables in power stations, industrial installations and switchgears, as well as in local mains. For fixed installation underground, in interior premises, cable ducts, in the open air and in water – as permitted by the local building regulations – if protection against shock hazard in the event of mechanical damage or electrical screening is required.
Design
This product consists of:
1
Copper conductor, round solid (RE) resp. round stranded (RM)
2
Core insulation (PVC)
3
Inner covering (EPDM)
4
Concentric screen (bare copper wires) and counter helix (copper tape) and optional plastic tape
5
Sheath (PVC black, UV-resistant)
Technical Data
Standard:
ÖVE/ONORM E 8200-603 (HD 603)
ÖVE/ONORM E 8200-627 (HD 627)
Certificate:ÖVE Austria
Test Voltage:core/core 4 kV / 50 Hz
Rated Voltage:0.6/1 kV
Bending radius (min.):
12 x Ø of cable (multicore)
15 x Ø of cable (singlecore)
Fire properties:
EN 60332-1-2: flame retardant and self-extinguishing
Our Code of Conduct and its associated regulations are not seeking to „invent“ new approaches. Instead, they aim to clearly demonstrate the obligations we must fulfill nowadays.