XLPE/FRNC motor power supply cable, halogen-free, screened
Automation and Motor Supply Cables
These double screened 2XSL(St)CH-J cables were designed as supply and connecting cables, for medium mechanical stress, for fixed installation and occasionally non-guided movements, in dry and damp rooms, especially where human life or valuable property are exposed to a high risk of fire hazards. Double screening considerably improves electromagnetic compatibility (EMC) in buildings and plants.
Design
This product consists of:
1
Bare copper conductors, fine wires class 5 according to DIN EN 60228 / VDE 0295 / IEC 60228
2
Core insulation of cross-linked polyethylene (XLPE)
3
Cores are stranded together with optimal lay-length
4
Plastic tape separation (optional)
5
Plastic bonded aluminium tape and tinned copper wire braiding
6
Outer sheath of special flame retardant non-corrosive compound (FRNC), clolour: black (RAL 9005)
Technical Data
Standard: DIN VDE 0276-603
Test Voltage: 4000 V / 50 Hz
Rated Voltage:
0.6/1 kV (Uo/U)
Bending radius (min.):
Fixed installation: 7.5 x Ø of cable
Flexible use: 15 x Ø of cable
Fire properties:
EN 60332-1-2: self-extinguishing and flame retardant
EN 60332-3-24 (Category C): reduced flame propagation
EN 61034: smoke density
EN 60754: halogen-free
CPR classification: Dca
Core identification: Colours according to CENELEC HD 308 S2
Earthing and Short Circuiting Cables and Bare Wires
Instalation and Harmonised Cables and Wires
Low Voltage Cables 0,6/1 kV
Safety Cables with circuit integrity
Medium Voltage Cables up to 36 kV