Double screened 2YSL(St)CY-J cables were designed as supply and connecting cables, for medium mechanical stress, fixed installation and occasionally non-guided movements, in dry, damp and wet rooms. UV-resistant black sheath is designed for outdoor applications. Double screening considerably improves electromagnetic compatibility (EMC) in buildings and plants.
Design
This product consists of:
1
Kupferleiter, feindrähtig
2
Aderisolation (PE), Adern mit optimaler Schlaglänge verseilt
3
Bebänderung (Kunststofffolie, optional)
4
Schirm (kunststoffkaschierte Aluminiumfolie und Geflechtschirm aus verzinnten Kupferdrähten)
5
Mantel (PVC, transparent (2YSL(St)CY-J) oder schwarz (2YSL(St)CYK-J))
Technical Data
Standard:DIN VDE 0276-603
Test Voltage:4 kV / 50 Hz
Rated Voltage:0.6/1 kV (Uo/U)
Bending radius (min.):15 x Ø of cable (free motion)
Fire properties:EN 60332-1-2: self-extinguishing and flame retardant